TimeMark Corporation Logo


Timemark Alternating Relay Model 261

Alternating Relays

 

  • Solid-state Reliability
  • Heavy-duty Contact Rating
  • Optional Load 1-Load 2 Toggle
  • UL Recognized; CSA Certified

 

Description

The Model 261 series Alternating Relay is designed for duplex pumping systems where it is desirable to equalize pump run time. The solid state alternating circuit drives an internal electromechanical relay. A continuous power source and control switch are required.

The control switch (float, pressure or other isolated contact) is connected between the L1 terminal and the control terminal. Each time the control switch is opened the output contacts will change states. Indicator lights on the case show the internal relay status.

On the optional toggle switch versions, the toggle switch is set to the NORMAL position. Setting the switch to Load 1 or Load 2 will lock the relay in position, preventing alternation.

 

Specifications

Model 261 x (T) - xxx
Supply Voltage 12V AC/DC 24V AC/DC 120V AC/DC 240V AC/DC
Voltage Range 10 - 14V 20 - 28V 90 - 130V 180 - 250V
Max Voltage 15V 30V 140V 260V
Supply Current 0.1A 0.05A 0.01A 0.01A
Control Current 0.001A
Operating Duty Continuous
Min. Cycle Time 100ms
Contacts 10A at 120VAC resistive
Expected Relay Life Mech: 10 million operations
Elec: 100,000 operations at rated load
Operating Temp 240V models: -20° to +131° F All other models: -20° to +140° F
Humidity Tolerance 0 - 97% w/o condensation
Mounting 261D: 11-pin socket
261S or 261DX: 8-pin socket
Enclosure Material ABS plastic
Weight 4.3 oz.
Agency Approvals UL Recognized (U.S. & Canadian)

Downloads

Document File Type File Size Download
Model 261 Datasheet PDF 715 KB