TimeMark Corporation Logo


Specifications

AUTO Reset A263 B263 C263 D263 EX263
MANUAL Reset A263M B263M C263M D263M EX263M
GOLD-AUTO Reset A263SG B263SG C263SG D263SG EX263SG
GOLD-MAN Reset A263SGM B263SGM C263SGM D263SGM EX263SGM
Nominal AC voltage (phase to phase) 120VAC 208/240VAC 480VAC 575VAC 380VAC
Adjustment Range 85-120V 160-240V 380-480V 450-575V 300-400V
Frequency 60Hz 60Hz 60Hz 60Hz 50Hz
Power Consumption 0.75W 1.5W 4.5W 7.5W 4.5W
Transient Protection 2500 VRMS for 10ms
Repeat Accuracy ± 0.1% of setpoint (fixed conditions)
Response Time 50ms
Dead Band Approximately 2%
Output Contacts All SG models: SPDT silver w/gold flash 5 amps at 240VAC resistive
All other models: SPDT 10 amps at 240VAC resistive
Expected Relay Life Mech: 10 million operations
Elec: 100,000 operations at rated load
Operating Temp - 20° to +131° F
Humidity Tolerance 0 - 97% w/o condensation
Enclosure Material ABS plastic
Mounting Surface
Weight 9.5 oz
Agency Approvals ALL VERSIONS - UL Recognized and CSA Certified

Downloads

Document File Type File Size Download
Model 263 Datasheet PDF 566 KB