TimeMark Corporation Logo


Specifications

Model 2532
Nominal voltage 190-500 VAC (phase to phase)
Frequency 50 to 60Hz
Power Consumption 2W per phase
Transient protection 2500 VRMS for 10ms
Repeat accuracy ± 0.1 % (fixed conditions)
Response time .05 seconds
Reset time .05 seconds
Reset type Automatic
Dead band Approximately 2 %
Output contacts SPDT 10A at 240VAC resistive
Expected relay life Mechanical: 10 million operations
Electrical: 100,000 at rated load
Operating temp - 20° to +131° F
Humidity tolerance 0-97 % w/o condensation
Case material ABS plastic
Mounting Surface
Weight 7 oz.
Agency approval UL Recognized and CSA Certified

Downloads

Document File Type File Size Download
Model 2532 Datasheet PDF 379 KB