Specifications

Model A246 B246 EX246
Nominal AC Voltage 120 208/240 380
Adjustment Range
Low:
High:

85-125 V
110-140 V

160-260 V
210-280 V

300-400 V
350-450 V
Frequency 60Hz 60Hz 50Hz
Power Consumption (per phase) 1W 1.5W 2W
Transient Protection 2500V for 10ms
Repeat Accuracy ±0.1% of set point (fixed conditions)
Response/Reset Time 50ms
Reset type Automatic
Dead Band 2%
Contact Rating SPDT 10A at 240VAC resistive
Expected Relay Life Mech: 10 million operations
Elec: 100,000 at rated load
Operating Temperature - 20° to +131° F
Humidity Tolerance 0-97% w/o condensation
Enclosure Material ABS plastic
Weight 6 oz.
Mounting 8-pin socket *order separately
Agency approval CSA CSA  

Downloads

Document File Type File Size Download
Model 246 Datasheet PDF 439 KB