The ISD Series of Intrinsically Safe Barrier Relays provide a safe and reliable
method to control up to four loads (motor starters, relays, etc.) with up to four input
devices (switches, sensors, etc.) located in a hazardous area.
The ISD Series relays utilize a compact 60mm wide enclosure that can be both
mounted on 35mm DIN rail or panel-mounted with two screws. Terminals for the
input devices from the hazardous area are on the bottom of the unit for easy access
in the enclosure to incoming field wiring from the hazardous area. Pluggable terminal
blocks on both the input and output sides allow for easy initial wiring of the unit as
well as replacement without having to remove any wires.
Each input has two terminals supporting direct connection of 2-wire input devices
eliminating the need to mount a separate terminal block. Each output relay is isolated
with two wiring terminals providing a true normally-open contact. This allows the output
contacts to be used in complex control circuits and allows for each output to switch
different voltages with respect to other outputs and the input voltage. A universal input
voltage of 102-132V AC & 10-125V DC covers a variety of applications with one
device.
Operation
Each ISD Series product consists of 4 intrinsically safe inputs and four
corresponding normally-open relay outputs. With input voltage applied, the V LED
will be ON (GREEN) to indicate power is applied. When the input device is closed,
the input LED is ON (GREEN). When the output relay is closed, the output LED is
ON (ORANGE). The ISD series offers four user-selectable configurations built in.
ISDUR4 has a two-position DIP-switch that selects a single configuration for all
channels.
ISDUM4 has an eight-position DIP-switch that selects a configuration for each
channel, independently.
Configurations
Standard Logic (DIP Switch set to “STD”):
When the input device is closed, the corresponding output contact is closed. When
the input device is open, the corresponding output contact is open.
Inverse Logic (DIP Switch set to “INV”):
When the input device is open, the corresponding output contact is closed. When
the input device is closed, the corresponding output contact is open.
No Time Delay (DIP Switch set to “0 S”):
The output contact changes state immediately in response to a change in input
device state.
2 Second Delay (DIP Switch set to “2 S”):
The output contact will delay 2 seconds before changing state in response to a
change in input device state.
Features
- Approved for use in these Hazardous Locations: Class I, Div 1 (Zones 0 and 1 Canada), Groups A, B, C, D; Class II, Div 1 (Zones 20 and 21 Canada), Group E, F, G; Class III, Div 1
- 4-Channel
- Terminals support 2-wire inputs
- Isolated 5A relay outputs
- Pluggable terminals offer easy installation & replacement
- Universal input voltage of 102-132V AC & 10-125V DC
- Compact 60mm wide enclosure for both DIN-rail or panel-mount
- Standard & inverse logic
- Instantaneous & delayed response times
- LED status indicator