Non-Latching Mode:
The unit will operate in the nonlatching
mode if no circuit is
completed across pins 9 & 11.
After input voltage is applied (LED
is Green) and the start-up sensing
delay (ts) of 0.1 – 10 seconds is
completed, the relay will energize
when the monitored current is above the adjustable pick-up setting (“Threshold”).
The LED will be Red. It will de-energize when the monitored current goes below the
adjustable drop-out setting (“Hysteresis”) by 5-50% of the selected pick-up setting
or when input voltage is removed. The LED will be Green
Latching Mode:
The unit will operate in the latching
mode if a N.C. contact (Memory S2)
is connected across pins 9 & 11 (see
Wiring Diagram). After input voltage
is applied (LED is Green) and the
start-up sensing delay (ts) of 0.1 –
10 seconds is completed, the relay
will energize when the monitored
current is above the adjustable pick-up setting (“Threshold”). The LED will be Red.
It will de-energize when the monitored current goes below the adjustable drop-out
setting (“Hysteresis”) by 5-50% of the selected pick-up setting and the N.C. contact
(Memory S2) is opened, or when input voltage is removed. The LED will be Green.
It is recommended to set the Hysteresis at 5% when in the latching mode.
Features