Specifications

Certifications UL Recognized, CSA, UL489, TUV, UL 1500
Number of Poles 1-3 poles
Available Delays Instant, Ultra-Short, Short, Medium, Long (motor loads), AC,DC, AC/DC; High Inrush - Short, Medium, Long
Maximum Current and Voltage Ratings UL Listed:
0.10-100A @ 80VDC
0.10-60A @ 125VDC
0.10-70A @ 120VAC
0.10-30A @ 240VAC

UL Recognized:
0.02-30A @ 480WYE/277VAC 2 pole 1 phase, 3 pole 3 phase
0.02-50A @ 277VAC
0.02-70A @ 250VAC, 80VDC
0.02-100A @ 120/240VAC, 65VDC
Maximum Interrupting Capacity UL Listed:
10,000A @ 120VAC, 80VDC
5,000A @ 240VAC, 125VDC

UL Recognized:
7,500A @ 80VDC
3,000A @ 125/250VAC (UL only)
5,000A @ 250VAC w/fuse back up
5,000A @ 480WYE/277VAC w/fuse back up
Auxiliary Switch Ratings 10.1A @ 250VAC
0.1A @ 125VAC (gold contacts)
5A @ 30VDC
Available Circuits Series, Shunt, Relay, Switch Only, Series Mid-Trip w/ Alarm Switch, Series w/Remote Shutdown, Relay and Shunt Trip Dual Coil
Actuator Style Handle (1 per pole)
Terminal Options .250 Double QC Tabs
10-32 Threaded Stud
10-32 Screw
10-32 Screw with Washer and Saddle Clamp
1/4-20 Threaded Stud
M5 Threaded Stud
M6 Threaded Stud
Push in Stud Terminals
Mounting Method Front Panel
Interface Options Flying Leads
Integral Connector
Flying Lead with 4 Pin Dual Row Connector
Remote Operator Input 12 VDC, 20-40VDC, 41-80VDC
Remote Operator Option Custom designed remote operated motor (housed within a circuit breaker molding), coupled to a Carling Technologies C-Series hydraulic/magnetic circuit breaker. The breaker can be operated manually, or remotely to control circuits for maintenance, load shedding and power distribution control functions from locations that are unattended or difficult to access. Some key features include:

* Design flexibility with multiple motor mounting options
* Remote operated module operates 1 - 3 poles
* Motor voltage input: 12 - 80 VDC
* Motor start current: <1 amp
* ON - OFF trip indication
* Load shedding capable
* Auto reset capable
Value Added Custom actuator colors
Non-standard amp ratings
Variety of Lead lengths
Din Rail construction available, consult factory

Documents and Downloads

Document File Type File Size Download
C Series Remote Operated Module Datasheet PDF 696 KB